OKet® flammable gas detectors are independently developed and produced by OKet®, based on the principle of non-dispersive infrared absorption. They are suitable for refueling stations, oil depots, petrochemicals, oil fields, coal mines, and other places where flammable gases exist in environmental protection and fire protection. It mainly monitors CH Combustible gas. When the detector reaches the alarm preset value, it will immediately send an alarm, and at the same time, the information will be transmitted to the flammable gas alarm controller of the alarm terminal, and the signal will be linked to the management and control platform to help managers to centralize and real-time the environmental conditions of all monitoring points monitoring.
Functions:
●Long life and high range.
●Real-time display of flammable gas concentration, sound and light prompt when reaching the alarm threshold.
●Fault self-check, display for normal, fault and alarm status.
●The alarm information can be uploaded online, which can be used in conjunction with other monitoring and early warning systems.
●Flameproof design, safe and stable.
There are two types of OKet® flammable gas detectors, wireless communication flammable gas detector ET01-L and wired communication flammable gas detector ET01.
ET01 wired communication flammable gas detector
ET01-L wireless communication flammable gas detector
Specifications:
Model | ET01 wired communication flammable gas detector | ET01-L wireless flammable gas detector |
Operating temperature | -40℃~70℃ | -20℃~60℃ |
Range | (0~100)%LEL25%LEL | (0~100)%LEL25%LEL |
Communication method | RS485/4~20mA/LoRa | LoRa |
Resolution | 1%LEL | 1%LEL |
High limit alarm | 50%LEL | 50%LEL |
Low alarm | 25%LEL | 25%LEL |
Accuracy | ±3%F.S(full range) | ±3%F.S(full range) |
Response time | ≤30s(T90) | ≤30s(T90) |
Protection level | IP65 | IP65 |
Explosion-proof type | Flameproof | Intrinsically Safe |
Explosion-proof sign | Ex d IIC T6 Gb | Ex d IIC T4 Gb |
Battery and charging frequency | —— | Detector spare battery 1, single charge can be used for 6 months |
Detectable gas | Benzene, gasoline, isobutane, propane, alcohols, n-butane, ethane, methane, natural gas... |
Flammable gas alarm controller
Features:
●Standard configuration can be connected to 24 channels of detectors, which can be expanded to 40 channels.
●Designed according to national standards, and some indicators are better.
●Perfect fault self-check: Support 19 kinds of fault state self-check, including power failure, loop failure, etc.
●The alarm threshold can be configured.
●Support leak sensors integration.
●Reserved communication interface to support the upload of alarm information.
●2000 alarm records are stored, and 1000 fault records are stored.
Specifications:
Model | LM-G1 Flammable gas alarm controller | LM-G2 Flammable gas alarm controller | G1-BL Flammable gas alarm controller |
Detector input signal | 4~20mA or RS485 | Wireless(LoRa) | Wireless(LoRa) |
Communication | RS485 | RS485 | RS485 |
Detector qty. | 24, Max.40 | Max.64(wireless) | 8, Max.24 |
Operating Voltage | AC220V±10% | AC220V±10% | AC220V±10% |
%3