1.DPLS-1 Dispenser Pan Leak Detection Sensor(discriminating)
DPLS-1 dispenser pan leak detection sensor is installed in the dispenser pan to monitor if there is any liquid exiting in real time. Any fuel/water presented in the bottom of dispenser pan will be tested and alarmed.
Functions:
● Water alarm
● Fuel alarm
● Short circuit alarm
● Open circuit alarm
● Can detect the hydrocarbon on the water, and trigger fuel alarm
Parameters:
● Temperature: -40℃~60℃(fuel); 0℃~60℃(no freezing water)
● Length of sensor cable: 2m
● Specifications: Length: 290mm; Diameter: 55mm
● Minimum alarm level: 4mm(fuel); 28mm(water)
● Minimum fuel thickness on water: 1mm
● Sensor accuracy: ≤2mm
● Enclosure protection class: IP68
Installation Diagram:
2.DPLS-2C Dispenser Pan Leak Detection Sensor
CSLS-2C manhole leak detection sensor is used to monitor whether liquid exits in the manhole. Self-detection function can detect open circuit or short circuit.
Functions:
● Liquid exits alarm
● Short alarm
● Open alarm
Parameters:
● Temperature: -40℃~60℃(fuel); 0℃~60℃(no freezing water)
● Length of sensor cable: 2m
● Specifications: Length: 545mm; Diameter: 55mm
● Sensor accuracy: ≤2mm
● Enclosure protection class: IP68
Installation Diagram:
Copyright Notice © 2015 QINGDAO OKET TECHNOLOGY CO., LTD.