Console Introduction:
MC-6 explosion-proof console is composed of magnetostrictive probe and leak sensor specially designed for mobile fuel station or outdoor ground tanks. By collecting ATG and environmental monitoring information, it visually displays oil information (level, volume,temperature) and environmental monitoring in the tank. And it can be connected with software platform and mobile phone link.
Structure Composition:
Function Introduction:
●Oil management
Real-time monitoring and leakage monitoring of fuel products in the tank. Various historical records inquiries (alarm records, fuel discharge records, tank storage records, density sensor records, pressure sensor records, operation records, switching recordss, shift records) Information uploading.
●Information uploading
The console has the function of uploading information. Supplementary transmission will be performed at regular intervals, and the supplementary transmission time and number of
supplementary transmissions can be set.
●Setup oil
The console can setup the oil products of each tank, sensor correlation and other information.
Interface Display:
History record interface, including: alarm record, oil discharge record, tank storage record, density sensor record, pressure sensor record, operation record, switching record, shift record. Alarm record interface, including: liquid level meter alarm, integrated leak detection alarm, combustible gas alarm, density sensor alarm, pressure sensor alarm.
Specifications:
Max number of monitoring tanks | 8 |
Explosion-proof mark | Ex db ia[ia Ga] ⅡB T6 Gb |
Protection class | IP66 |
Power supply | AC 220V |
Rated current and power | 88W |
Operating current | 0.4A |
AC frequency | 50Hz |
Installation Location | 1zone 2zone |
Relative humidity | 5~95%RH |
Storage temp | -40℃~60℃ |
Operating temperature | -40℃~60℃ |
Installation & Maintenance:
●Installation Preparation
The console is powered by a 220V power supply. It must be connected with the on-site grounding system by a wire > 4mm², and shall not be shared with other equipment, and the connection resistance should be < 1Ω.
●Installation Precautions
Don’t install with power on. See the installation manual for details. Professional operation.
●Explosion-proof precautions
During maintenance and repair, it is strictly forbidden to open it with electricity! It is strictly forbidden to damage the explosion-proof surface! The lead-in must be pressed tight! It is strictly forbidden to use ferrous metal or tools that are prone to sparks to beat, hit and work in the oil and gas area. It is strictly forbidden to wear clothing that is easy to generate static electricity and shoes with iron nails to work in the oil and gas area.
●Maintenance & Care
Without professional guidance, it is strictly forbidden to disassemble the explosion-proof console, leak detection sensor, liquid level meter and other related components at will; make the explosion-proof console dustproof and waterproof, especially in rainy days, please wipe the water stains on the explosion-proof console in time. ; Pay attention to the operation of the equipment in time; if the damage is more serious, please contact the manufacturer for repair in time.
Installation & Maintenance advantage:
1. The console is easy to install and easy to operate.
2. It has passed the explosion-proof certification and protection level certification, and the product has excellent outdoor performance.
3. The size of the display screen is large, which is easy to monitor and view real-time data outdoors.
4. Equipped with sound and light alarm system, you can find out whether the connected equipment is abnormal in time in the outdoor environment.
5. This console supports a variety of device connections, which can meet all the demands of gas stations.
Copyright Notice © 2015 QINGDAO OKET TECHNOLOGY CO., LTD.
No.16 Shanghai Rd,Free Trade Zone, Qingdao City, China
+86-532-86769572
Powered by MetInfo